- 型号:
- AWQ
Working principle of dry steam humidifier: The dry steam humidifier humidification system adopts foreign advanced steam-water separation technology and steam-water separation mechanism to introduce filtered saturated steam into the saturated steam inlet, and the saturated steam moves laterally in the nozzle jacket , flows circumferentially into the elbow and enters the evaporation chamber. Due to the sudden increase in the section of the evaporation chamber, the steam decelerates. Coupled with the inertia effect and the obstruction of the baffle, the condensed water contained in the steam is separated and discharged from the condensed water outlet. The clean steam containing moisture enters the preheated drying chamber from the top of the separation chamber. The drying chamber is filled with stainless steel filter materials. The remaining moisture in the steam is filtered and separated. The regulating valve is opened. The pressure in the drying chamber drops and the vaporization temperature drops. , the moisture remaining in the steam is heated and vaporized again, thus completing the drying process of the saturated steam and the separation of steam and water from the saturated steam. The dry steam enters the nozzle through the regulating valve and is sprayed from the metal mesh with silencer. It sprays out of the hole to humidify the air.
Features of dry steam humidifier:
. Introducing foreign advanced water vapor separation technology to make the separation of steam and water more thorough.
. The external type uses a unique double-layer casing and silencer device to ensure that the dry steam emitted will never spray water or whistle.
3. Electric and electromagnetic dry steam are integrated structures, which can realize remote and precise control of humidity.
.The built-in type can help users solve the problem of limited installation space.
.It belongs to isothermal clean humidification and has high humidification efficiency, which can reach above.
. Made of all stainless steel 3() material, it has beautiful appearance, easy installation, corrosion resistance and long life.
. The maximum humidification capacity of a single unit can be achieved/reliable performance and easy installation.
Dry steam humidifier selection
Dry steam humidifier selection steps
) According to the designed or calculated humidification amount and saturated steam pressure (for standard selection, the saturated steam pressure is.) , look up the table to determine the suitable dry steam humidifier model.
) Select the model of the spray boom according to the width of the air conditioning unit or air duct.
3) Determine the left and right type of dry steam humidifier according to the form or installation requirements of the air conditioning unit.
Generally, if the air conditioning unit is of the right type, a right-type dry steam humidifier should be installed. On the contrary, a left-type dry steam humidifier should be installed. Only in this way can it be ensured that the sprayed dry steam is in the opposite direction of air flow.
Determination rules for left-hand and right-hand dry steam humidifiers. Looking from the evaporator to the direction of the spray boom, if the direction of steam ejected from the spray boom is to the right, then the dry steam humidifier is left-hand type. Otherwise, the dry steam humidifier is left-hand type. Right style.
) Select the adjustment method according to the control requirements. Note: In order to make the humidity adjustment more accurate, it is necessary to choose an electric or pneumatic proportional actuator. If the switch control mode is used, a certain amount of condensed water will be generated under instantaneous saturation, which will cause problems such as reduced humidification accuracy.
Things to note when installing the dry steam humidifier humidification host:
The humidifier should be installed within the absorption distance, otherwise a multi-nozzle humidifier should be used, and the nozzles should be in line with the direction of the air flow.
The end of the nozzle should be slightly tilted upward so that the condensed water can flow back into the flash chamber.
The nozzle should be installed at least 10 meters away from the downstream side of the surface cooler.
Keep at least the above distance between the humidifier nozzle and the control sensing element.
The nozzle should be installed between the heater and the muffler as much as possible to help eliminate steam injection noise.
When installing multiple nozzles, the spacing between the nozzles should be equal.