Hello and welcome toTitker Trade Network!
Manufacturing, processing and sales of electrical equipment, power

free member

VS1-12 side-mounted vacuum indoor high-voltage circuit breaker factory direct sales

价格 3100.00元/台
total supply
100 台
MOQ
1 台
brand
申恒电力设备
area
ZhejiangWenzhou city
Delivery period:
Shipped within 3 days from the date of payment by the buyer
Buyers are still looking
  • 1
  • 2
  • 3
Products Recommended

Factory direct sales

¥3480.00/台

Outdoor high voltage

¥3288.00/台

Factory direct sales

¥3500.00/台

ZGS-12/0.4 prefabric

¥3500.00/台

VS1-12 side-mounted

¥3100.00/台

FZN25-12D/T630 vacuu

¥1299.00/台

Shop information

area:Zhejiang Wenzhou city

Member level:corporate memberYear1

identity:   

Already paid:0.00 yuan deposit

my badge: [Integrity File]

online service:

Business card

Shenheng Electric Power Equipment Co., Ltd.

Applets
【Kind tips】When you call, please mention that you saw us on Titker Trade Network, thank you.
Product Details
额定电压:
12KV
额定电流:
630A
额定频率:
50HZ
&Overview:
The side-mounted vacuum circuit breaker is an indoor high-voltage switching device. It is suitable for use in three-phase power systems with rated voltage and frequency as protection and control appliances. Due to the special advantages of vacuum circuit breakers, It is especially suitable for places that require frequent operation at rated current or multiple short-circuit currents.
The side-mounted vacuum circuit breaker adopts fixed installation and is mainly used in fixed switch cabinets. The breaker can be used alone or in ring network power supply, box-type transformer or various non-standard power supply systems. .
Conditions of use
) The ambient temperature is not higher than +℃ and not lower than &℃ (storage and transportation are allowed at ℃)
) The altitude is not higher than
) Relative temperature: day The average value is not greater than %, the monthly average is not greater than %, the daily average saturated vapor pressure is not greater than .&, the average value is not greater than .&
) The earthquake heat does not exceed excessive
) There is no fire or explosion risk , places with serious pollution, chemical corrosion and severe vibration.
Working principle
. Energy storage action
The energy required for closing the circuit breaker is provided by the energy storage of the closing spring. Energy storage can be accomplished by an external power supply driving the motor, or it can be accomplished manually using an energy storage handle.
Energy storage operation: The energy storage motor fixed on the frame is energized and outputs torque, and drives the sprocket to rotate through the one-way bearing of the motor output shaft, or the energy storage handle is inserted into the manual energy storage hole and shakes clockwise, through the worm gear (,) drives the sprocket to rotate. Then the chain drives the sprocket to rotate. When the sprocket rotates, the gear pin pushes the slider on the wheel to make the energy storage shaft follow the rotation, and the closing springs are stretched by the arms on both sides to store energy. When the energy storage position is reached, the frame The limit lever presses down the slide to disengage the energy storage shaft from the sprocket transmission system. The energy storage holding detent resists the roller to maintain the energy storage position. At the same time, the dial on the energy storage shaft drives the energy storage indicator plate to flip, showing that it has been stored. Energy storage mark, and switch the travel switch to cut off the power supply of the energy storage motor. At this time, the circuit breaker is in a closing preparation state.
.Close operation
After the mechanism stores energy, if a closing signal is received, the closing electromagnet will act or the closing button will be pressed to cause the stored energy to keep the shaft rotating and drive the detent to release the roller. Release the energy storage hold, and the closing spring releases energy, causing the energy storage shaft and the cam on the shaft to rotate clockwise. By rotating the crank arm, the transmission connecting plate drives the insulating pull rod to drive the moving contact upward to the closing position, and compresses the contact The head spring maintains the required contact pressure of the contacts.
After the closing action is completed, the closing detent and half shaft maintain the closing position. At the same time, the energy storage indicator board and energy storage travel switch are reset, the motor power supply circuit is connected, and the closing and opening indicator board displays the &r mark. , if the external power supply is also connected, it will enter the energy storage state again.
Note: When the circuit breaker is already in the closing state or the locking device is selected without connecting to the external power supply, and the handcart type circuit breaker is in the process of being pushed, the closing operation cannot be performed.
.Opening operation
After the closing action is completed, once the opening signal is received or the opening button is pressed, the opening tripping electromagnet or the overcurrent tripping electromagnet will act, causing the opening half shaft to align The constraints of the closing holding latch are released. The energy stored in the contact spring and the opening separates the dynamic and static contacts of the arc extinguishing chamber to realize the opening operation. In the latter part of the opening process, the hydraulic buffer absorbs the remaining energy of the opening process and defines the opening position.
The closing and opening indicator board displays the "minute&r mark, and the counter is pulled at the same time to realize the counter counting, and the transmission connecting rod pulls the main auxiliary switch to switch.
Installation, debugging
.Unpacking
When lifting the circuit breaker from the packaging box, the hook should be hung on the crane with obvious signs on the circuit breaker. When moving, the upper and lower outlet arms must not be subject to any damage. force, and the circuit breaker should not be subject to large shock and vibration.
Inspection before installation
The circuit breaker has undergone strict factory inspection before leaving the factory, and the parameters all meet the technical requirements. The following preparations must be made before energizing the primary circuit.
.Check the product nameplate, whether the certificate of conformity is consistent with the order form, and whether the packing list is consistent with the actual product.
b. Check whether the circuit breaker is damaged. If damaged, please stop using it.
c. Clear the dust and dirt on the surface, especially the insulating surface, and check the vacuum degree of the vacuum arc extinguishing chamber using the manual withstand voltage method (open the circuit breaker and apply power frequency between the fractures)
&.Use Manually operate the circuit breaker according to the regulations to store energy, close and open. Observe the energy storage status and whether the opening and closing indication position is normal. (Note: The circuit breaker equipped with a locking device must be operated manually after the secondary circuit is energized)
&. Use the operating power supply to operate the circuit breaker for energy storage, closing and opening, observe the energy storage status, and Check whether the closing indicator position is normal
To operate the hand truck type circuit breaker, follow the following steps: insert the push handle into the hole, and shake it clockwise to push it in, and shake it counterclockwise to pull it out. The total push stroke is approximately in the opening state. It should enter the working position or experimental position smoothly. Please turn the handle ring at a medium speed. When you hear a "click" sound, it is in place (do not use excessive force to damage the propulsion structure). At the same time, connect the corresponding position indication loop.
Note: Before entering the cabinet, please remove the lifting device as required.
Disclaimer

The information/pictures/parameters, etc. displayed on this webpage about【VS1-12 side-mounted vacuum indoor high-voltage circuit breaker factory direct sales】are provided by member【Shenheng Electric Power Equipment Co., Ltd. 】,By Titker Trade Network members 【Shenheng Electric Power Equipment Co., Ltd. 】is solely responsible for the authenticity, accuracy and legality of the information/pictures/parameters, etc.,Titker Trade Network only provides display services. For your safety, please choose Titker Trade Network for online trading, otherwise Titker Trade Network will not bear any responsibility for this.

If your legitimate rights and interests have been infringed, please contact Titker Trade Network customer service as soon as possible. We will serve you wholeheartedly. Thank you for your attention and support to Titker Trade Network!

Titker Trade Network