Yangzhou Zhongnan brand valve position transmitter
converts the potentiometer signal of the valve position into an analog signal and feeds it back to the control system.
Setting steps
After the wiring is correct according to the drawing, power on, the power indicator light is on, press the setting button to enter the setting state, the fully closed indicator light flashes, adjust the valve to the fully closed position, press the setting button to confirm the fully open indication The lights flash. In the same way, adjust the valve to the fully open position, press the setting button to confirm, and the transmitter will automatically exit the setting state.
If the output needs to be adjusted, press the adjustment key to enter the output current adjustment state. At this time, connect the multimeter to the current output section and press the setting button repeatedly to observe the changes in the output current. When the output current is , press the adjustment key to determine the output current corresponding to the fully closed position. In the same way, after setting the current value corresponding to the fully open position, the transmitter automatically exits the current adjustment state.